Inspection
Inspection Details
Equipment ID
23428
23428
Inspection Date
8/8/2018
8/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
8dbec59f-7498-4349-bbcb-1cc7db1b4f72
8dbec59f-7498-4349-bbcb-1cc7db1b4f72
Location
4534 Olive LLC
4534 OLIVE ST, SAINT LOUIS, MO
4534 OLIVE ST, SAINT LOUIS, MO
Owner
Jewel of the Plaza LLC
393 N EUCLID AVE, SAINT LOUIS, MO 63108-1288
393 N EUCLID AVE, SAINT LOUIS, MO 63108-1288
Billing
Attn: Red Brick Management
393 N EUCLID AVE, SAINT LOUIS, MO 63108-1288
393 N EUCLID AVE, SAINT LOUIS, MO 63108-1288
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide up to date test tag on fire extinguisher. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on site maintenance records and monthly elevator fire log. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Existing battery back up system does not work. | 6/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide fire extinguisher and test it annually. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | Brake does not hold 125% capacity. Re-inspection required | 7/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram the emergency phone to call a monitored station | 4/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Repair inoperative emergency light | 4/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Emergency rescue unit does not work, battery has no power, Re-inspection required | 10/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Overhead machine space lighting does not work and is not mounted properly, needs repaired. Re-inspection required | 10/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Overhead machine space lighting does not work and is not mounted properly, needs repaired. Re-inspection required | 4/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Top of hoistway lights are not working, repair as needed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | All hoistway doors are missing bottom door fire tabs, provide. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. |