Inspection
Inspection Details
Equipment ID
217
217
Inspection Date
3/31/2022
3/31/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Kurzava
Benjamin Kurzava
Relief Valve Pressure
Slide
6"
6"
Governor Rope Pull
75/500
75/500
Door Closing Force
20
20
External ID
97cdf6ec-5c78-449d-88e0-4df4a0fa0040
97cdf6ec-5c78-449d-88e0-4df4a0fa0040
Location
Heritage Towers
515 W MOUNT VERNON ST, SPRINGFIELD, MO
Phone: (417) 207-4888
515 W MOUNT VERNON ST, SPRINGFIELD, MO
Phone: (417) 207-4888
Owner
Attn: Chuck Hicks
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (417) 207-4888
Email: Chicks@hasproperties.org
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (417) 207-4888
Email: Chicks@hasproperties.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 1/5/21:: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8). 4x4 electrical box (Phone wiring) in machine room needs to have wiring inside box and cover installed. | 3/31/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | H(6). Machinery, controllers, governors, disconnects shall be numbered conspicuously. | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/16/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/16/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG) | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed | 3/31/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG) | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed | 3/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 5/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | remove rubbish and material from machine room floor | 6/26/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace the hoist ropes due to undersizing | 6/26/2025 |