Inspection
Inspection Details
Equipment ID
13988
13988
Inspection Date
4/15/2022
4/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
952e4a71-4710-4efd-bdda-a930dc26aed5
952e4a71-4710-4efd-bdda-a930dc26aed5
Location
Coronado Place
3701 Lindell Blvd, St. Louis, MO
Phone: (918) 575-0716
Email: Thomas.brown@coronadoplaceandtowers.com
3701 Lindell Blvd, St. Louis, MO
Phone: (918) 575-0716
Email: Thomas.brown@coronadoplaceandtowers.com
Owner
Attn: St. Louis Properties
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
St. Louis Properties
3701 Lindell Blvd, St. Louis, MO 63108
Phone: (918) 575-0716
Email: cm@coronadoplaceandtowers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable emergency phone. | 4/17/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 3/1/2021 |
| MO Minimum : Elevators | (D) - Brakes | (D)1 | Yes | Yes | Car brake failed to hold 125% - red tagged | 4/15/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Incomplete test - check fire service, buffer, safeties, slide, phone/lights/alarm bell. | 4/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean car top and pit. | 2/6/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Elevator pit light shall work with a minimum of 5 foot candles. | 2/6/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be clean of all debris | 2/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Elevator car top shall remain clean to prevent any hazards | 2/6/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on 110v emergency power or normal power. Repair or replace | 8/13/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the machine room in a noncombustible frame. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room does not close completely and latch. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting shall work | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be free of oil and debris. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. |