Inspection
Inspection Details
Equipment ID
25572
25572
Inspection Date
3/31/2022
3/31/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Michael Vantassel
Michael Vantassel
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
29F/29R
29F/29R
External ID
3c94e2c2-09ca-4d21-9d10-4b5d6c2d4c3e
3c94e2c2-09ca-4d21-9d10-4b5d6c2d4c3e
Location
Old Judge Building, LLC
710 N 2nd St, St. Louis, MO
Phone: (314) 260-9266
710 N 2nd St, St. Louis, MO
Phone: (314) 260-9266
Owner
Attn: Alan Luffy
Advantes Group
701 N 1st St, St. Louis, MO 63102
Phone: (314) 260-9266
Email: accountspayable@advantesgrp.com
Advantes Group
701 N 1st St, St. Louis, MO 63102
Phone: (314) 260-9266
Email: accountspayable@advantesgrp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational with 110v source removed. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Provide fire service Phase 2 instructions inside the car. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install missing electrical box covers on the car top. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The hoist ropes shall have data tags installed. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | All electrical wires in the hoistway shall be enclosed in conduit or metal raceway, or be in compliance with NFPA 70. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car operating panel shall be secured. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways shall be fully enclosed and made of solid construction. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Unit shall have a code compliant code data plate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Install missing duct covers and electrical box covers in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The pit door shall be self-closing and self-locking. It is also recommended that a warning/danger sign be put on the pit door. | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase 2 fire service switch shall be two position type. Shall not have bypass feature operational. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire alarm initiating devices (smoke detectors) shall be provided and shall active Phase 1 fire service. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fire service Phase 2 key switch shall be operational. Unit Red Tagged. | 6/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | All car top electrical boxes shall have covers installed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "In Case of Fire" signage shall be installed at each landing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 3/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational with 110v source removed. | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The building is in the process of adding smoke detectors to the elevator and testing will be required when complete. Elevator not red tagged. | 3/31/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Counterweight guards shall extend from a point not more than 12" above the pit floor to a point not less than 7' above the pit floor. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The walk-in pit door shall be self-closing. | |
| A17.1-2016 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(cc) | No | No | The car and counterweight retaining clips shall be spaced correctly. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A governor rope data tag shall be provided. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. A maintenance check chart and wiring diagrams are the only items present. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Label the disconnect with the location, source, and breaker numbers of the panel from which it is fed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. |