Inspection
Inspection Details
Equipment ID
17548
17548
Inspection Date
4/14/2022
4/14/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
7fabd582-cf44-4896-aa28-4fd2df92f27e
7fabd582-cf44-4896-aa28-4fd2df92f27e
Location
Chase Park Plaza Hotel
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
Owner
Attn: Paul Smith
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Billing
Attn: Accounts Payable
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: AP-FS-StLouis-MO@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: AP-FS-StLouis-MO@sonesta.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Stop switch needs to be overridden on Phase 1 | 3/31/2026 |
| conversion | conversion | n/a | No | No | Emergency light not working | 3/31/2026 |
| conversion | conversion | n/a | No | No | The heat detector needs to be 2 ft or less from sprinkler heads | 3/31/2026 |
| conversion | conversion | n/a | No | No | Seal all penetrations in the hostway | 3/31/2026 |
| conversion | conversion | n/a | No | No | Pit needs to be clean and dry. Remove oil and debris | 3/31/2026 |
| conversion | conversion | n/a | No | No | Sprinklers in hoistway at top. Need smoke detector and heat detectors at top of hoistway | 3/31/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Top floor door closer on hoistway door is broken. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit is covered in oil. Clean | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | In car stop switch is not overridden on Phase I Fire Service when car is in flight. | 3/19/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil soaked pit pads. | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Overspeed valve is not sealed. Perform OSV test on or before next annual inspection. | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Car stop switch not overridden on Phase I | 4/14/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Install heat and smoke detectors at top of hoistway and less than 2 ft from sprinkler head in machine room and pit. Did not red tag. | 4/14/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Repair hoistway penetrations in machine room around piping. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 1. Replace broken limit switch roller at top hoistway. Rule G-1, Missouri minimum. Rule 8.11.3.1.3(F) A17.1, 2016. Rule 3.6, A17.2, 2014. | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | 2. Overspeed valve is not sealed and needs full load test and tripping speed checked. Rule 8.6.5.16.5, A17.1, 2016.Reinspect by 7-14-22(90 days) | 4/14/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Repair top floor hoistway door closer. Missing Hardware | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing roller on top directional switch | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged roller on car top slow down switch | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil soaked pads from elevator pit | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | In car stop switch shall be overridden on phase 1 fire service. Rule s-1 this violation has been written up multiple times. Repair and reinspect by 5-14-23 (30 days) or elevator wil be red tagged and removed from service | 9/18/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Elevators hoistway shall be fully enclosed to their full height | 3/31/2026 |