Inspection
Inspection Details
Equipment ID
17738
17738
Inspection Date
8/25/2017
8/25/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
480
480
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
28
28
External ID
17738
17738
Location
Forest Park Station
250 DeBaliviere, St. Louis, MO
Phone: (314) 289-6870
250 DeBaliviere, St. Louis, MO
Phone: (314) 289-6870
Owner
Metro Accounts Payable
707 N, 1st St., St. Louis, MO 63188
707 N, 1st St., St. Louis, MO 63188
Billing
Attn: Metro Accounts Payable
P.O. Box 1349, , MO 63188
P.O. Box 1349, , MO 63188
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 11/4/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | Stop switch not working. | 7/23/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post State certificate in machine room | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance conttrol program on site posted on controller | 11/4/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need fire service log posted in machine room to be be tested monthly | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Water damage on electric disconnects in machine room | 11/4/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | Yes | OSV test performed, elevator would not level at top landing and kept hitting stop ring. Red tagged elevator. | 7/28/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 7/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Severe water damage. | 7/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean oil from elevator pit. | 11/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | No | Cylinder head on hydraulic jack has leaking packing seal, need to replace seal. Re-inspection required | 10/26/2023 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required | 1/17/2025 |