Inspection
Inspection Details
Equipment ID
20470
20470
Inspection Date
9/16/2021
9/16/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
006998f0-f18d-4e29-a741-041de8a82af5
006998f0-f18d-4e29-a741-041de8a82af5
Location
Crowder College Health & Life
601 Laclede Ave, Neosho, MO
Phone: (000) 000-0000
601 Laclede Ave, Neosho, MO
Phone: (000) 000-0000
Owner
Attn: Crowder
Crowder College- Neosho
601 Laclede Ave, Neosho, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Crowder College- Neosho
601 Laclede Ave, Neosho, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone will not call out | 7/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | Yes | Fire Service "reset" shall work properly Reinspect within 30days | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | Yes | Front/rear floor markings (PI, button braille, open/close buttons/hall braille) shall be consistent and properly labeled. Reinsp 30days | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | ire Service "reset" shall work properly Reinspect within 30days | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Front/rear floor markings (PI, button braille, open/close buttons/hall braille) shall be consistent and properly labeled. Reinsp 30days | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 7/12/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean, free of excessive debris and oil. | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired | 4/27/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects) | 10/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) | 11/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and free of excessive oil/debris. (Reported as compliant on 4/27/22, ) NOT compliant as of this inspection | 11/16/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019) | 11/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | 6.5.9.3 Phase 2 switch does not initiate auto-recall after turning from ON to OFF. All other functions are proper. (Works if switch wiring is "jiggled". repair properly) | 10/24/2022 |