Inspection
Inspection Details
Equipment ID
14695
14695
Inspection Date
4/7/2022
4/7/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
John Palmer, Jr
John Palmer, Jr
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
11c2a68b-8907-4a91-89e7-9e898315d983
11c2a68b-8907-4a91-89e7-9e898315d983
Location
Assumption Parish- O'Fallon - Church
405 N Main St, O'Fallon, MO
Phone: (636) 240-3721
405 N Main St, O'Fallon, MO
Phone: (636) 240-3721
Owner
Attn: Mark Vogt
Assumption Parish- O'Fallon
403 N Main St, O'Fallon, MO 63366
Phone: (636) 240-3721
Email: mvogt.abvm@gmail.com
Assumption Parish- O'Fallon
403 N Main St, O'Fallon, MO 63366
Phone: (636) 240-3721
Email: mvogt.abvm@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state and local operating certificate. | 7/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 8/7/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 7/14/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 7/14/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 4/7/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 7/14/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 4/7/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/14/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 2/14/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/7/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 7/14/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 4/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: The disconnect is equipped with the required auxiliary contact, but is not wired to the elevator system. | 4/30/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/7/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/14/2025 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 7/14/2025 |