Inspection
Inspection Details
Equipment ID
17737
17737
Inspection Date
8/25/2017
8/25/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
540
540
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
30
30
External ID
17737
17737
Location
Forest Park Station
250 DeBaliviere, St. Louis, MO
Phone: (314) 289-6870
250 DeBaliviere, St. Louis, MO
Phone: (314) 289-6870
Owner
Metro Accounts Payable
707 N, 1st St., St. Louis, MO 63188
707 N, 1st St., St. Louis, MO 63188
Billing
Attn: Metro Accounts Payable
P.O. Box 1349, , MO 63188
P.O. Box 1349, , MO 63188
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Per NEC, repair disconnect and replace 4x4 box cover. | 11/4/2020 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Disconnect is rusting out due to water damage. | 11/4/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 11/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site posted on controller | 11/4/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need fire service log posted in machine room to be tested monthly | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Water damage on electric disconnects in machine room | 11/4/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Severe water damage. | 7/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting is not working, needs to be repaired | 11/7/2023 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | Yes | No | Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required | 10/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 11/4/2025 |