Inspection
Inspection Details
Equipment ID
963
963
Inspection Date
4/21/2022
4/21/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
15
15
External ID
5dfa354b-7d2a-49b4-9173-d4601d79d5fd
5dfa354b-7d2a-49b4-9173-d4601d79d5fd
Location
Parkview Place
701 WESTGATE AVE, UNIVERSITY CITY, MO
Phone: (314) 721-7067
701 WESTGATE AVE, UNIVERSITY CITY, MO
Phone: (314) 721-7067
Owner
Attn: Parkview Housing Corp
Parkview Housing Corp
701 Wastgate Ave, University City, MO 63130
Phone: (314) 721-7067
Fax: (314) 721-4875
Email: parkviewoffice@fairwaymanagement.com
Parkview Housing Corp
701 Wastgate Ave, University City, MO 63130
Phone: (314) 721-7067
Fax: (314) 721-4875
Email: parkviewoffice@fairwaymanagement.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not being answered. | 9/30/2020 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Repair front door restrictor within 14 days. | 9/30/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Remove water from the pit. | 12/13/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Repair cab ceiling light fixture, missing ceiling tile. | 12/13/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Annual inspection incomplete - need to test fire service. | 4/5/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Phone line problem | 11/29/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 4/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car does not work. Re-inspection required | 6/3/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be cleaned | 4/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work | 4/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car shall be guarded to protect passengers in event of bulb breakage. Need to install solid ceiling panels or plastic tubes and endcaps over bulbs | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room shall provide at least 19 fc illumination at floor in front of controller | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all materials not related to elevators from machine room | 4/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Counterweight runby is less than 6". Hoist ropes need to be shortened. Re-inspection required | 6/3/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Unable to place car calls in Phase II fire service operation, needs repair. Re-inspection required | 6/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car does not work. Re-inspection required | 4/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car shall be guarded to protect passengers in event of bulb breakage. Install solid ceiling panels or plastic tubes and endcaps over bulbs. | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room shall provide at least 19 fc illumination at floor in front of controllers. | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all materials not related to elevators from machine room | 4/27/2026 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door restrictor shall be made operational. Re-inspection required | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car shall be guarded to protect passengers in event of bulb breakage. Install solid ceiling panels or plastic tubes and endcaps over bulbs. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room shall provide at least 19 fc illumination at floor in front of controller |