Inspection
Inspection Details
Equipment ID
1433
1433
Inspection Date
4/19/2022
4/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
585fb6a3-fcd2-40f2-84ce-5f6c646ff45e
585fb6a3-fcd2-40f2-84ce-5f6c646ff45e
Location
Macy's- South County
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-0110
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-0110
Owner
Attn: Cathie Sherman
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
MACY'S MSOC VERTICAL COMPLIANCE
237 Woodbridge Center Dr, 3rd Flr, Woodbridge, NJ 07095
Phone: (732) 734-3438
Email: Cathie.Sherman@macys.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | Yes | Brake test failed.. RED TAGGED out of service | 11/8/2018 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | step has broken tread, needs replacing | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Need code compliant caution signage at bottom | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Two com plates missing tooth needs replacing | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | Full clean down of truss needed | |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.6.8.6 | No | No | Step thread broken needs replacing | |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(b) | No | No | Need maintenance control plan and place on controller | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.7 Rollers, Tracks, and Chains | Yes | No | Repair step chains. Unit red tagged | 11/19/2021 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace broken (chipped) treads | 10/19/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Step indexing failed reinspection item 30 day maximum | 2/6/2025 |
| A17.1-2016 : Elevators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.15.1 | No | No | Clean machine pits at upper and lower ends. | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post certificate in machine room. |