Inspection
Inspection Details
Equipment ID
1875
1875
Inspection Date
8/17/2018
8/17/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
91546789-5f77-4f2e-b92c-852ff65951e0
91546789-5f77-4f2e-b92c-852ff65951e0
Location
Ameren Missouri
1901 CHOUTEAU AVE, SAINT LOUIS, MO
1901 CHOUTEAU AVE, SAINT LOUIS, MO
Owner
Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103-3003
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103-3003
Billing
Attn: Ameren U E
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103-3003
1901 CHOUTEAU AVE, SAINT LOUIS, MO 63103-3003
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working | 6/6/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working | 8/17/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car is running with the car door open. | 2/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 2/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 2/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 2/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. Repair the self-closing device. | 5/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | The enclosed stop switch in the pit shall meet A17.1 1995 which requires the switch to be marked red. | 5/13/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Provide pit light to work. | 11/19/2025 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.4.1 | No | No | Minimum bottom clearance for counterweights shall measure no less than 6.5 inches. Measurements for this inspection proved 5 inches. Ropes shall be shortened. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The emegency phone shall establish 2-way communication. |