Inspection
Inspection Details
Equipment ID
16952
16952
Inspection Date
4/14/2022
4/14/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Jason Turner
Jason Turner
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
83e0334b-91c4-4d08-a140-5e6aa93725b6
83e0334b-91c4-4d08-a140-5e6aa93725b6
Location
Independence Center
2035 E Independence Center Dr, Independence, MO
Phone: (816) 795-8602
2035 E Independence Center Dr, Independence, MO
Phone: (816) 795-8602
Owner
Attn: IGP Business Group
IGP Business Group
5919 W. 3rd Street, Suite B, Los Angeles, CA 90036
Phone: (816) 795-8602
IGP Business Group
5919 W. 3rd Street, Suite B, Los Angeles, CA 90036
Phone: (816) 795-8602
Billing
Attn: Independence Mall Holding LLC
Independence Mall Holding LLC
18801 E. 39th Street South, Suite 2035, INDEPENDENCE, MO 64057
Phone: (816) 795-8602
Email: thueser@shopindependencecenter.com
Independence Mall Holding LLC
18801 E. 39th Street South, Suite 2035, INDEPENDENCE, MO 64057
Phone: (816) 795-8602
Email: thueser@shopindependencecenter.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no cirt. of operation displayed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 4/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | no fire extinquisher in mach. room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 11/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | no fire extinquisher in mach room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | mcp not current | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | operating cirt. not current | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | no fire extinquisher in mach. room | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone answered but security couldnt tell me my location | 2/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | no fire extinquisher in mach room | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | no fire Extinqisher in mach room |