Inspection
Inspection Details
Equipment ID
18731
18731
Inspection Date
7/27/2018
7/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Thomas Jimas
Thomas Jimas
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
16F/20R
16F/20R
External ID
d3dcdc0b-49c1-4683-8106-0c874967ccfa
d3dcdc0b-49c1-4683-8106-0c874967ccfa
Location
America's Best
6602 S LINDBERGH BLVD, SAINT LOUIS, MO
6602 S LINDBERGH BLVD, SAINT LOUIS, MO
Owner
Anand Gorani 4, Inc
1310 BASS PRO DR, SAINT CHARLES, MO 63301-2461
1310 BASS PRO DR, SAINT CHARLES, MO 63301-2461
Billing
Attn: Anand Gorani 4, Inc
1310 BASS PRO DR, SAINT CHARLES, MO 63301-2461
1310 BASS PRO DR, SAINT CHARLES, MO 63301-2461
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | A completed fire service testing log shall be kept on-site. | 11/26/2019 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | Phase 2 fire service operating instructions in the car are worn and unreadable and shall be replaced. | 11/26/2019 | ||
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 1001.2(a)(16) | The capacity plate in the car is worn and unreadable and shall be replaced. | 11/26/2019 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display the current state operating certificate. | 11/26/2019 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/27/2021 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO state operating certificate shall be displayed in the elevator machine room. | 11/27/2021 | ||
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/27/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit has an excessive amount of water in it. Take corrective action as needed. | 11/22/2022 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The auxiliary power lowering operation shall be functional. | 5/30/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The fire service phase one key-switch bezel shall be legible. | 11/12/2024 | ||
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 207 | A capacity plate listing the capacity in pounds and prominently displayed in the car enclosure. | 11/12/2024 | ||
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | The machine room light fixture shall be properly fastened to the ceiling in a permanent fashion. | 11/12/2024 |