Inspection
Inspection Details
Equipment ID
7152
7152
Inspection Date
4/19/2022
4/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
6aebf280-6352-4c5b-b2cc-2d53744fed1c
6aebf280-6352-4c5b-b2cc-2d53744fed1c
Location
HoteLumiere
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Attn: Pinnacle Entertainment
Pinnacle Entertainment
3800 Howard Hughes Pkwy, Las Vegas, NV 89169
Phone: (000) 000-0000
Pinnacle Entertainment
3800 Howard Hughes Pkwy, Las Vegas, NV 89169
Phone: (000) 000-0000
Billing
Attn: HoteLumiere
HoteLumiere
901 N 1st St, St. Louis, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
HoteLumiere
901 N 1st St, St. Louis, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean oil off of floor and machine. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace broken clutch roller and 4th floor. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated cert in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean cartop of dirt and debris. | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lights shall be guarded. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wire in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door should be self closing and locking. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wires in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 4/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace clutch rollers on doors for floor 4 and 7 | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights not adequate | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency back up lights not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs to be serviced or replaced. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 1/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Clean machine room floor of oil leaking from machine, need to repair leaks | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean cartop | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protect passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self locking and self closing | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lights are not working | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove water from pit. Repair / replace sump pump | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted from water in pit, needs replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car buffer channel is rusting out due to water in pit. Refurbish/replace same | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made to work when car looses 110 vac. Re-inspection required | 1/8/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made to work car looses 110vac. | 4/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate has been expired for several years. A copy of current valid certificate needs to be displayed in machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room floor of oil leaking from machine, repair leaks. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean car top | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protect passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in pit shall work | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit. Repair/replace sump pump | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car side selector cable is rusted from water in pit. Replace same. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car buffer channel is rusting out due to water in pit. Refurbish/replace same. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | Yes | The elevator was removed from service for having existing violations for consecutive years in a row. All violations shall be corrected before the elevator is returned to service and the annual insepection is completed. | 4/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Elevator cab phone does not work on normal or back-up power. Elevator has not had a phone for over a year and a half. Elevator Red-tagged and removed from service. Re-inspection required | 7/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean cartop | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protest passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted from water in pit. Need to be replaced | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean cartop of dirt and debris. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wire in machine room. Need to be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car side selector cable is rusted from water in the pit, needs to be replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Machine need cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted and shall be replaced | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car light shall be guarded | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wired for AC/Thermostat shall be enclosed in conduit and boxes | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs cleaned |