Inspection
Inspection Details
Equipment ID
17258
17258
Inspection Date
4/5/2022
4/5/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
4869f770-c0db-49e7-b0c5-24c71951094a
4869f770-c0db-49e7-b0c5-24c71951094a
Location
Norwood Court/Redfield
4620 Redfield Ct, Normandy, MO
Phone: (314) 381-9555
4620 Redfield Ct, Normandy, MO
Phone: (314) 381-9555
Owner
Attn: Kristin Johnson
St Louis 5 2022 LLC dba Norwood Court/Redfield
7217 Woodstead Ct, St. Louis, MO 63121
Phone: (000) 000-0000
Email: Kristin.Johnson@multi-south.com
St Louis 5 2022 LLC dba Norwood Court/Redfield
7217 Woodstead Ct, St. Louis, MO 63121
Phone: (000) 000-0000
Email: Kristin.Johnson@multi-south.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept dry. Determine the source of the fluids entering the pit and repair as needed. | 4/19/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall work. | 4/19/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Repair or replace the damaged cab ceiling light. | 4/19/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 6/24/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove water from the pit and clean the pit. | 6/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/24/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The safety edge re-opening device is not operating properly. | 6/13/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump in pit. Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas.” | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove the water in the pit. |