Inspection
Inspection Details
Equipment ID
18506
18506
Inspection Date
7/18/2018
7/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
c7d9a847-e5df-4a4d-a77d-24b7c10735cc
c7d9a847-e5df-4a4d-a77d-24b7c10735cc
Location
Walnut Street Station
151 E FRONT ST, WASHINGTON, MO
151 E FRONT ST, WASHINGTON, MO
Owner
City of Washington
405 JEFFERSON ST, WASHINGTON, MO 63090-2607
405 JEFFERSON ST, WASHINGTON, MO 63090-2607
Billing
Attn: City of Washington
405 JEFFERSON ST, WASHINGTON, MO 63090-2607
405 JEFFERSON ST, WASHINGTON, MO 63090-2607
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)10 | Yes | No | Unit is tagged as having a category 5 full load safety test in 2018, but there is no proof of that test happening. Verification of the Category 5 full load safety test is required. If verification is not found, a Category 5 test is required. | 6/29/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted on or near the equipment in a noncombustible frame with a clear protective vision plate over it. | 2/5/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | The in car alarm bell shall be operational on auxiliary power. Note: Elevator Red Tagged due to no working emergency communication device. | 7/21/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 1200.6 | No | No | A code data plate shall be provided on the controller. | 2/5/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 2/5/2026 |
| A17.1-1996 : Elevators | 3.16 - Traveling cables and junction boxes | 1001.2(c)(22) | No | No | The traveling cable must be run in raceway to the controller. Note: Currently, the T-cable leaves the hoistway, and runs to the controller without being enclosed. | 2/5/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted near the lift. | 11/3/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Four hour battery back up required for emergency alarm or two-way communication. The two way communication device shall be operational on regular power and on battery power. | 11/3/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate is expired. | 2/5/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | The fire extinguisher is expired. | 2/5/2026 |