Inspection
Inspection Details
Equipment ID
5841
5841
Inspection Date
4/13/2022
4/13/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
26F/25R
26F/25R
External ID
4d0d1038-e4da-4176-926e-ef227cf36c75
4d0d1038-e4da-4176-926e-ef227cf36c75
Location
Convergys- Village Square
41 Village Square Shop Ctr, Hazelwood, MO
Phone: (314) 432-7600
41 Village Square Shop Ctr, Hazelwood, MO
Phone: (314) 432-7600
Owner
Attn: Village Square Partners I LLC
Village Square Partners I LLC
15 Village Square Shop Ctr, Hazelwood, MO 63042
Phone: (000) 000-0000
Village Square Partners I LLC
15 Village Square Shop Ctr, Hazelwood, MO 63042
Phone: (000) 000-0000
Billing
Attn: Convergys Village Square
Village Square Partners I LLC
8300 Eager Rd, Ste 601, St. Louis, MO 63144
Phone: (000) 000-0000
Email: jburke@dcmstl.com
Village Square Partners I LLC
8300 Eager Rd, Ste 601, St. Louis, MO 63144
Phone: (000) 000-0000
Email: jburke@dcmstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/11/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | All cab lights shall work. | 1/22/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 1/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 1/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Phone dials, but there is no answer. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that they cannot be opened more than 4 inches from inside the car. Add needed brackets for front and rear. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room (falsely reported as compliant 1/22/25). | 9/20/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired and guarded against breakage, 1 or more bulbs not working. | 9/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | All lamps shall work and be guarded to keep broken glass from falling onto passengers (falsely reported as compliant 1/22/25). | 9/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Violation still exists as of 9/15/25. | 5/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Violation still exists as of 9/15/25. | 5/20/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired and guarded against breakage. One or more bulbs are not working. Violation still exists as of 9/15/25. | 5/20/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | All lamps shall work and be guarded to keep broken glass from falling onto passengers. Violation still exists as of 9/15/25. | 5/20/2026 |