Inspection
Inspection Details
Equipment ID
8272
8272
Inspection Date
4/26/2022
4/26/2022
Inspection Type
Alteration
Alteration
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jason Bock
Jason Bock
Relief Valve Pressure
470
470
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
05888a8d-3a1e-4bb0-8a5e-6114dde0bfe1
05888a8d-3a1e-4bb0-8a5e-6114dde0bfe1
Location
America's Center
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
Owner
Attn: America's Center
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Clean oil and oil dry off pit floor | |||
| conversion | conversion | n/a | Alarm bell inoperative need repair | |||
| conversion | conversion | n/a | Reduce door closing force pressure, both sides | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit shall be kept clean and dry. Clean oil and dry pit. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | Method of oil collection shall not exceed 5 gal. Repair leaking cylinder head seal. Scavenger pump is for temp use leak is fixed. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | x | x | Door closing force on both doors exceeds maximum, adjust to correct setting and reinspect upon repair. | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide written maintenance control program to be kept on site. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Unit not working | 7/29/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | x | A copy of the MCP shall be kept in the machine room for each elevator | 7/29/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Piston packing worn and leaking, repair as needed. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current certificate. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit has significant amount of oil in it, remove. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | Sump pump in the pit is under oil, replace if needed. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in car not working correctly. | 12/7/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide MCP. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV needs to be tested in 90 days or less. Re-inspection required | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current operating certificate shall be displayed in the machine room | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | Replace worn cylinder packing rings to reduce leakage | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean pit to remove debris, water and/or oil and address sources | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Sump pump under oil, replace if needed | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Car emergency signal failed Cat 1 Emergency Communications test. Re-inspection required | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Need to provide a MCP |