Inspection
Inspection Details
Equipment ID
23274
23274
Inspection Date
4/13/2022
4/13/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Jacob Williams
Jacob Williams
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
8b887bd6-8231-4422-baf2-8202d381941e
8b887bd6-8231-4422-baf2-8202d381941e
Location
Anthology of Clayton
8825 EAGER RD, SAINT LOUIS, MO
Phone: (314) 961-1700
8825 EAGER RD, SAINT LOUIS, MO
Phone: (314) 961-1700
Owner
Attn: Chuck
Anthology of Clayton
8825 Eager Rd, St. Louis, MO 63144
Phone: (314) 961-1700
Email: claytonviewbod@anthologyseniorliving.com
Anthology of Clayton
8825 Eager Rd, St. Louis, MO 63144
Phone: (314) 961-1700
Email: claytonviewbod@anthologyseniorliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 10/26/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Weights shall not be stored on the car top. | 2/18/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean. | 10/20/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | x | The middle door hanger and bottom fire gib are missing from all hoistway doors. | 4/13/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | An ABC type fire extinguisher is required in the vestibule near the controller at the top landing. | 10/20/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/20/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The door data tag needs to be completed. | 10/20/2023 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)11 | Adjust the retaining clips on the suspension ropes so they are properly spaced. | 10/20/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | x | x | Unit Red Tagged due to main brake not holding rated load. | 4/13/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Test the main brake with 125% of capacity. | 4/13/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Test the emergency brake with 125% of capacity. | 4/13/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Set the safeties with 100% capacity. | 4/13/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Check unintended motion in both directions. | 4/13/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | x | The middle door hanger and bottom fire gib are missing from all hoistway doors. | 4/22/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | x | x | Unit Red Tagged due to main brake not holding rated load. | 4/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Test the main brake with 125% of capacity. | 4/22/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Set the safeties with 100% capacity. | 4/22/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Due to the unit being red tagged, the following items still need to be tested: Check unintended motion in the down direction | 4/22/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | x | The middle door hanger and bottom fire gib are missing from all hoistway doors. | 2/17/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean the pit of oil, dirt, and debris. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/14/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | The emergency rescue device shall be operational. Note: This device brings the car level into the floor and opens the door in the event of main power failure. | 1/30/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. Note: The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. | 1/30/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/21/2025 | ||
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Pit shall be kept clean. |