Inspection
Inspection Details
Equipment ID
20867
20867
Inspection Date
4/15/2022
4/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
8aeb9470-4506-4aca-81b4-039946d2fac9
8aeb9470-4506-4aca-81b4-039946d2fac9
Location
Confluence Prep II
310 N 15th St, St. Louis, MO
Phone: (000) 000-0000
310 N 15th St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Michael Baker
Confluence Academy, Inc
611 N 10 St, Ste 525, St. Louis, MO 63101
Phone: (314) 588-8554 Ext: 7031
Email: mbaker@confluenceacademy.org
Confluence Academy, Inc
611 N 10 St, Ste 525, St. Louis, MO 63101
Phone: (314) 588-8554 Ext: 7031
Email: mbaker@confluenceacademy.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator pit floor is submerged in water. The elevator pit shall be kept clean and dry. | 3/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 11/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | The emergency rescue device shall be operational. | 6/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, need to replace or have serviced | 4/16/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP is incomplete, need to update & fill out, including monthly fire service checks | 4/16/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency rescue standby device is not working. Re-inspection required | 5/21/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Governor rope (6.5 millimeter) is rouged and needs to be replaced. Re-inspection required | 10/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Elevator pit light fixture was full of water and has no electrical power. Repair or replace elevator pit light to provide a functional light fixture. | 4/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery Lowering operation is currently inoperable and shall be repaired or replaced. Reinspection required. | 8/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery Lowering operation is currently inoperable and shall be repaired or replaced. Reinspection required. |