Inspection
Inspection Details
Equipment ID
17988
17988
Inspection Date
8/30/2018
8/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
ee2637d0-f9ae-47ad-babc-466b9b6f0d1e
ee2637d0-f9ae-47ad-babc-466b9b6f0d1e
Location
Boehringer Ingelheim Vetmedica Inc
2621 N BELT HWY, SAINT JOSEPH, MO
2621 N BELT HWY, SAINT JOSEPH, MO
Owner
Boehringer Ingelheim Vetmedica Inc
2621 N BELT HWY, SAINT JOSEPH, MO 64506-2002
2621 N BELT HWY, SAINT JOSEPH, MO 64506-2002
Billing
Attn: Boehringer Ingelheim Vetmedica Inc
2621 N BELT HWY BLDG F, SAINT JOSEPH, MO 64506-2002
2621 N BELT HWY BLDG F, SAINT JOSEPH, MO 64506-2002
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | post emergency evacuation of passengers procedure form inside machine room. | 3/15/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | post code data plate on controller or disconnect. | 3/15/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site | 3/21/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 3/21/2023 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room access door needs to be self-closing | 3/21/2023 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or disconnect. ASME A17.1 1996 | 3/21/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting does not illuminate. Fluorescent lamps are burned out. | 3/21/2023 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 3/21/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No MCP | 11/2/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | 11/2/2023 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine access door shall be self-closing | 11/2/2023 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or disconnect. | 11/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 11/2/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | NO MCP | 10/24/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | NO MAINTENANCE RECORDS | 10/24/2024 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | POST '' IN CASE OF FIRE '' SIGNAGE NEXT TO HALL STATION AT EACH LANDING | 10/24/2024 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | POST ''CORRECT'' DATA PLATE ON CONTROLLER OR DISCONNECT | 10/24/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | MACHINE ROOM DOOR SHALL BE SELF CLOSING | 10/24/2024 |