Inspection
Inspection Details
Equipment ID
14222
14222
Inspection Date
5/5/2022
5/5/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Sam Cones
Sam Cones
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
86d1a9cd-bf51-49bd-9a35-c08d30c13d75
86d1a9cd-bf51-49bd-9a35-c08d30c13d75
Location
The Lofts at Jordan Creek
601 N NATIONAL AVE, SPRINGFIELD, MO
Phone: (417) 865-8698
601 N NATIONAL AVE, SPRINGFIELD, MO
Phone: (417) 865-8698
Owner
Attn: Brentwood Management Inc
Brentwood Management Inc
1050 E Walnut, Ste A, SPRINGFIELD, MO 65806
Phone: (417) 865-8698
Email: doug@springfieldlofts.com
Brentwood Management Inc
1050 E Walnut, Ste A, SPRINGFIELD, MO 65806
Phone: (417) 865-8698
Email: doug@springfieldlofts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Phone Failed | 8/3/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed | 8/16/2019 |
| A17.1-2016 : Elevators | 2.2 - Headroom | 8.11.3.1.2(c) | No | No | Must Maintain 84" clear head height in Mach Room. (Recently add conduits at 5'-10"must be removed from the Machine room.) | 6/27/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.3.1.2(j) | No | No | Must Provide current Test tag on Mach room Fire Extinguisher. | 6/27/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. | 5/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.2 Headroom | 8.11.2.1.2(b) | No | No | Must remove or relocate 2-3" conduits above/ Infront of Controller to maintain 7'clear headed height. | 6/27/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current State operating Cert. in Mach. room | 6/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.2 Headroom | 2.7.4 | No | No | Must remove 3" conduit in machine room at 5'-11" height must maintain clear 7" head height in Machine room. 2.7.4 | 6/21/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post Current State operating Cert. in Machine room. 5.100(2) | 6/27/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency Phone operable. 8.6.4.15 | 6/12/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current Annual test tag on Machine room Fire Extinguisher. ( currently tagged 5/21) | 6/27/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 8.6.4.15 | 11/22/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emegency phone operable. 8.6.4.15 | 6/6/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 1.6 | 8/4/2025 |