|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
5/21/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
Yes
|
No
|
The car door restrictor bracket is missing on the 2nd floor hoistway door. The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
5/21/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
The fire extinguisher in the machine room shall be serviced.
|
5/21/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
The code data plate found on the equipment to indicate the code and edition that the elevator shall be inspected to indicates an incorrect referenced code. The correct referenced code shall be State of Missouri Minimum Elevator Safety Code 11 CSR 40-5.065. Provide a proper plate on the front of the controller or mainline disconnect.
|
5/21/2019
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
|
5/21/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work with power off.
|
12/21/2020
|
|
A17.1-2016 : Elevators
|
5.5 - Traveling cables
|
8.11.3.1.5(f)
|
No
|
No
|
Traveling cables are cloth jacket and exposing cables. Jacket is worn, replace.
|
4/27/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Car failed 15 minute standing test. Tech determined leak through valve. Repair/retest.
|
5/5/2022
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
No
|
No
|
Door force exceeds 30 lb pressure, adjust as needed.
|
4/27/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
Update on-site maintenance records.
|
4/27/2022
|