Inspection
Inspection Details
Equipment ID
13934
13934
Inspection Date
5/6/2022
5/6/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Ross Colligan
Ross Colligan
Relief Valve Pressure
Slide
6
6
Governor Rope Pull
40 / 400
40 / 400
Door Closing Force
na
na
External ID
e0fadd00-efce-42b9-96b5-a997a09eea47
e0fadd00-efce-42b9-96b5-a997a09eea47
Location
Riverview Distributing Pumping Station
10450 Riverview Dr, St. Louis, MO
Phone: (314) 868-5640
10450 Riverview Dr, St. Louis, MO
Phone: (314) 868-5640
Owner
Attn: City of St. Louis Water Division
City of St. Louis Water Division
10450 Riverview Dr, St. Louis, MO 63137
Phone: (314) 592-8515
Email: scymerman@stlwater.com
City of St. Louis Water Division
10450 Riverview Dr, St. Louis, MO 63137
Phone: (314) 592-8515
Email: scymerman@stlwater.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair hoistway access chain covers and boxes top and bottom floor | 3/4/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell not working | 3/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site. | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Service or replace fire extinguisher. | 11/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)4 | No | Yes | Car buffer and pit channel rusted out. Replace. Red tagged elevator. | 4/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program needs to be kept on site for each elevator. | 11/5/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 11/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs serviced or replaced | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide rail fastening in pit below rail has deteriorated and needs to be replaced | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Emergency door release devices need to be replaced with a lockable cover at the top & bottom floors. Re-inspection required | 5/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Basement door needs to be adjusted so that it can be opened properly. | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide rail fastening in pit below rail has deteriorated and needs to be replaced | 11/5/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lights are not working in machine room | 5/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher has expired, needs to be replaced or serviced | 5/1/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Water in Pit, approx 2-3 inches. Sump Pump is not working. |