Inspection
Inspection Details
Equipment ID
17772
17772
Inspection Date
8/28/2018
8/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
22
22
External ID
a784b178-12c2-4814-9861-8f6138c49138
a784b178-12c2-4814-9861-8f6138c49138
Location
Bee Hat Apartments
1021 WASHINGTON AVE, SAINT LOUIS, MO
1021 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Bee Hat Apartments
1021 WASHINGTON AVE, SAINT LOUIS, MO 63101-1294
1021 WASHINGTON AVE, SAINT LOUIS, MO 63101-1294
Billing
Attn: Bee Hat Apts
PO BOX 1345, SAINT LOUIS, MO 63188-1345
PO BOX 1345, SAINT LOUIS, MO 63188-1345
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light in car doesn't work | 7/13/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing water in pit. Sump pump bot working | 6/5/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone fails to dial out | 6/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | -A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. | 6/5/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | Electrical Piping to car buffer is rusted away. Buffer switch wiring is exposed on pit floor. | 6/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 1/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is 4 inches of water in the pit. The sump pump is not working. All pits shall be kept clean and dry | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | The sump hole cover has corroded to the point that it is broken in half. All sump holes shall be provided with a cover | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light is not functioning. | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The sump pump is not functioning. Means shall be provided to prevent the accumulation of water in elevator pits. | 6/5/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The large penetration in the hoistway wall where the sump pump piping is ran into the pit needs to be sealed. | 6/5/2026 |