Inspection
Inspection Details
Equipment ID
18358
18358
Inspection Date
8/30/2018
8/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
1027dc6f-2eba-4e5f-a152-d4d5c932a93d
1027dc6f-2eba-4e5f-a152-d4d5c932a93d
Location
McCullough Condos
231 MCCULLOUGH AVE, KIRKWOOD, MO
231 MCCULLOUGH AVE, KIRKWOOD, MO
Owner
Parc McCullough Condo Association
231 MCCULLOUGH AVE, KIRKWOOD, MO 63122-5862
231 MCCULLOUGH AVE, KIRKWOOD, MO 63122-5862
Billing
Attn: Parc McCullough Condo Association
231 MCCULLOUGH AVE UNIT 1, KIRKWOOD, MO 63122-5863
231 MCCULLOUGH AVE UNIT 1, KIRKWOOD, MO 63122-5863
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit broke during inspection - The safeties shall be tested as part of a category 5 test. | 10/13/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested. | 10/13/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 6/16/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire Extinguisher is out of date. | 8/12/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The elevator went down during the inspection. The car is stuck on the safeties. Elevator left out of service by elevator maintenance company. | 9/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to complete inspection due to unit getting stuck on safeties. The following testing items still need to be performed and witnessed to complete the annual inspection. Remaining testing items: Set safeties again, test fire service, testing of governor, testing of car & counterweight buffers, and scan of the hoistway. | 9/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete due to rated speed being listed at 200 FPM, but the elevator is only running at 125 FPM. The weight portion of the 5-year test shall be completed. | 8/25/2026 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 206.5 Governor Ropes | Yes | Yes | Governor rope is frayed and shall be replaced. Unit out of service until replaced and reinspected. | |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | No | No | Operating Control Devices: Phone button and phone symbol damaged in COP, currently being held in place by tape. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency Battery Power/Rescue system shall be tested and operation verified. |