Inspection
Inspection Details
Equipment ID
11069
11069
Inspection Date
5/16/2022
5/16/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
a42a8393-4d33-498e-a617-0a98d3521940
a42a8393-4d33-498e-a617-0a98d3521940
Location
Matthews Elementary
144 NE McQuerry Rd, Grain Valley, MO
Phone: (816) 229-4870
144 NE McQuerry Rd, Grain Valley, MO
Phone: (816) 229-4870
Owner
Attn: Grain Valley R-5 School District
Grain Valley R-5 School District
PO Box 304, Grain Valley, MO 64029
Phone: (000) 000-0000
Grain Valley R-5 School District
PO Box 304, Grain Valley, MO 64029
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current operating cirt. displayed | 9/16/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | no sump pump cover 1061b(4) | 9/16/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | sump pump pluged into GFI outlet in pit no non gfi out let for sump pump | 5/11/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | no smoke detectors in mach room or in the hallway. | 5/11/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide non combustable cover for sump pump in pit. | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide non combustable cover for sump pump in pit. | 9/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Provide smoke detectors in each elevator lobby, and machine room. | 10/5/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Smoke detectors present, but not connected to the controller. Complete installation, and re-inspect. | 5/9/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a non combustable cover for sump pump in pit. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 5/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights and alarm not working, phone ok. | 5/29/2025 |