Inspection
Inspection Details
Equipment ID
15252
15252
Inspection Date
4/29/2022
4/29/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
680c30fe-c420-44cb-94ac-ca268fdf755e
680c30fe-c420-44cb-94ac-ca268fdf755e
Location
BRDG Park
1005 N Warson Rd, St. Louis, MO
Phone: (314) 995-3717
1005 N Warson Rd, St. Louis, MO
Phone: (314) 995-3717
Owner
Attn: Cushman & Wakfield
VTR LS Danforth
575 Maryville Centre Dr, Ste 115, St. Louis, MO 63141
Phone: (000) 000-0000
Email: luke.hesse@cushwake.com
VTR LS Danforth
575 Maryville Centre Dr, Ste 115, St. Louis, MO 63141
Phone: (000) 000-0000
Email: luke.hesse@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 4/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 7/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. The test is not being logged monthly. | 7/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 8/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | A capacity plate listing the capacity in pounds shall be provided and prominently displayed in the car enclosure. The capacity/car identification plate is illegible and shall be repaired or replaced. | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. The capacity/car identification plate is illegible and shall be repaired or replaced. | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | A two-way communication means between the car and a location staffed by authorized personnel shall be provided. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and free of oil and debris. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and free of oil and debris. Existing self-certify violation not checked at time of phone re-inspect. Violation to be certified as corrected by owner. | 11/26/2025 |