Inspection
Inspection Details
Equipment ID
24719
24719
Inspection Date
5/17/2022
5/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
55e3667a-b16d-4194-bbf0-f9008ffb97c5
55e3667a-b16d-4194-bbf0-f9008ffb97c5
Location
SSM SLUH Hospital Garage
1125 S Grand Blvd, Saint Louis, MO
Phone: (314) 602-1152
Email: patrick.schubert@ssmhealth.com
1125 S Grand Blvd, Saint Louis, MO
Phone: (314) 602-1152
Email: patrick.schubert@ssmhealth.com
Owner
Attn: Brandy Kary
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 257-1152
Email: brandy.kary@ssmhealth.com
Billing
Attn: Patrick Schubert, Director, Plant Operations
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Patrick.schubert@ssmhealth.com
SSM SLU Hospital
1201 S Grand Blvd, St. Louis, MO 63110
Phone: (314) 257-1152
Email: Patrick.schubert@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The belt monitoring device, that monitors the hoist belts, was not monitoring one of the belts. The hoist belt was thoroughly inspected visually and no deterioration was detected. There was no fault code showing immediate replacement. The hoist belt monitor shall be repaired or replaced to monitor all belts used for hoisting the car.. Reinspection is required. | 6/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. The ADA location for this elevator is incorrectly stating it as “parking garage elevator #1”. Reprogram this feature to correctly identify this elevator as “parking garage elevator #2” for proper operation and passenger safety. Reinspection required. | 6/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | The lighted direction arrow, inside the car, on the left side incorrectly lights the wrong direction of travel. Repair direction arrow to operate as designed. | 5/27/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | No | The coated steel belt monitoring device (pulse unit) is not monitoring one of the belts, needs repaired. Re-inspection required | 5/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone is not working correctly, speaker works, but the microphone does not. Re-inspection required | 5/20/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean dirt and debris from elevator pit | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work. Re-inspection required | 6/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean dirt from elevator car top | 5/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test phase I and II fire service. Re-inspection required | 6/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test is incomplete, need to perform the following tests to complete inspection: Test car buffer at rated speed with rated load, test counterweight buffer at rated speed, test car safeties with rated load at rated speed, test drive machine brake with 125% of the rated load, test unintended car movement with 125% of rated load. Re-inspection required | 6/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | No | No | The coated steel belt monitoring device (pulse unit) is not monitoring one of the belts, needs repaired | 5/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean dirt and debris from elevator pit | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A!7.2 shall be kept in the elevator machine room | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | No | No | The coated steel belt monitoring device (pulse unit) is not monitoring one of the belts, needs repaired | 5/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean dirt and debris from elevator pit | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 5/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test Phase I & II fire service. Re-inspection required | 7/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | No | No | The coated steel belt monitoring device (pulse unit) is not monitoring one of the belts, needs repaired | 5/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean dirt and debris from elevator pit | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 5/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | The lighted direction arrow, inside the car, on the left side incorrectly lights the wrong direction of travel. Repair direction arrow to operate as designed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room |