Inspection
Inspection Details
Equipment ID
6623
6623
Inspection Date
8/6/2018
8/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
680
680
Slide
Governor Rope Pull
Door Closing Force
22/22
22/22
External ID
22bffe2c-c830-4edb-8217-22e93a2dec9f
22bffe2c-c830-4edb-8217-22e93a2dec9f
Location
JC Penney- STL
50 HAMPTON VILLAGE PLZ, SAINT LOUIS, MO
50 HAMPTON VILLAGE PLZ, SAINT LOUIS, MO
Owner
The Desco Group
25 N BRENTWOOD BLVD, SAINT LOUIS, MO 63105-3709
25 N BRENTWOOD BLVD, SAINT LOUIS, MO 63105-3709
Billing
Attn: The Desco Group
25 N BRENTWOOD BLVD, SAINT LOUIS, MO 63105-3709
25 N BRENTWOOD BLVD, SAINT LOUIS, MO 63105-3709
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean elevator pit | 5/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. (Repeat Violation) | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | The light switch in the machine room shall be a toggle switch. The automatic switch shall be removed. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and dry. Remove water and trash from the pit. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 3.27 The in car emergency telephone shall be operational. (Repeat Violation) | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | The light switch in the machine room shall be a toggle switch. The automatic switch shall be removed. | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | 8.6.4.7 The pit shall be kept clean and dry. Remove water and trash from the pit. | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate. | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.1.6.5 Fire Extinguishers | No | No | No fire extinguisher located in machine room. |