Inspection
Inspection Details
Equipment ID
15027
15027
Inspection Date
5/16/2022
5/16/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
c5e7f88e-7fe6-4eb4-9240-90f5c8f4c535
c5e7f88e-7fe6-4eb4-9240-90f5c8f4c535
Location
Iatan Power Plant
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
Owner
Attn: Kevin Cook
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: kevin.cook@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: kevin.cook@evergy.com
Billing
Attn: Steven Thomas
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: steven.d.thomas@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: steven.d.thomas@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove standing water on machine room floor. AC unit in machine room leaking water onto floor. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Provide means for ascending car and unintended movement protection. Existing rope gripper does not function correctly. | 4/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emg. lt. an bell not working phone works but is the wrong kind | 5/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit covered in water | 1/1/2024 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | hoistway access sws. not working | 1/1/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | incomplete MCP | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not illuminate | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | All elevators in the same building shall have firefighter keyswitches operated by the same key | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | No | No | Interior of controller and its components need to be cleaned of coal dust | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Layer of coal dust covering entire machine room and equipment needs to be removed | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | hoistway access switches do not function. | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | machine room air conditioner does not work | 1/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | car firefighter operation panel needs to have a lockable cover | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone button on car operating panel does not activate the phone | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/24/2024 |