Inspection
Inspection Details
Equipment ID
16280
16280
Inspection Date
3/25/2022
3/25/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Richard Fuller
Richard Fuller
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
16F/23R
16F/23R
External ID
fbbf8320-7df0-44ee-abbb-a09a8514c859
fbbf8320-7df0-44ee-abbb-a09a8514c859
Location
Harrah's Casino- NKC
1 Riverboat Dr, N Kansas City, MO
Phone: (816) 889-4265
Alt Phone: (816) 365-6915
1 Riverboat Dr, N Kansas City, MO
Phone: (816) 889-4265
Alt Phone: (816) 365-6915
Owner
Attn: Harrah's Casino- NKC
Harrah's Casino- NKC
1 Riverboat Dr, N Kansas City, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Harrah's Casino- NKC
1 Riverboat Dr, N Kansas City, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the elevator pit, there is an oil and water mixture on the pit floor. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | replace the emergency light battery, it is dead. | 8/17/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | repair/replace sheetrock for the machine room wall that was removed to repair water lines in the wall. | 7/14/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | finish cleaning the pit, pig mat is not to be left on the pit floor | 5/18/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is to be updated every year | 5/18/2022 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket | 10/26/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | standing oil on the pit floor, clean the pit | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | repair the pickup rollers assemblies on both landings, on the bottom landing the stop bolt is bent and on the top landing the stop bolt is sheared off | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Recovery pump in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5 | 10/24/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing oil on pit floor, clean the pit, replace leaking Victaulic couplings | 10/24/2024 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | Adjust car door force to be 30 lbs or less on both the front and rear car doors | 5/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove scavenger pump from pit | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post permit in cab or other specified location | 7/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil absorbent pads from the pit floor | 7/18/2025 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.4 Maintenance Records | No | No | Provide update maintenance task log | 7/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | fire service phase 2 did not work in accordance with the instructions on the car operating panel, did not return to the recall floor | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | the door restrictor on the front opening needs to be adjust to work | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | provide "in case of fire use stairs" sign on the top landing near the hall button fixture |