Inspection
Inspection Details
Equipment ID
8786
8786
Inspection Date
9/14/2017
9/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
420
420
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
28
28
External ID
8786
8786
Location
Corporate Plaza Bldg
14528 S Outer 40, Chesterfield, MO
Phone: (314) 336-2362
14528 S Outer 40, Chesterfield, MO
Phone: (314) 336-2362
Owner
Realty Assoc Iowa Corp
120 S Central Ave, Ste 500, St. Louis, MO 63105
120 S Central Ave, Ste 500, St. Louis, MO 63105
Billing
Attn: Realty Assoc Iowa Corp
120 South Central suite 500, , MO 63105
120 South Central suite 500, , MO 63105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove Oil from pit floor | 12/2/2019 |
| conversion | conversion | n/a | No | No | Repair Fire Service--Car does not come off fire service when Phase I switch is placed in bypass | 12/2/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Make car door restrictors operational | 9/10/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace sections of missing duct covers in hoistway between L & 1st floor | 12/2/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Post current State certificate in machine room | 12/2/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program shall include written procedures for inspections and test on site. | 11/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 11/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | None | 6/14/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/14/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV in the pit is due for testing, provide. | 4/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. | 5/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State operating permit shall be obtained and displayed in the equipment room. | 5/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. | 5/16/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service operation shall be tested monthly and documented on fire service testing log. No log present. | 5/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). | 5/16/2025 |