Inspection
Inspection Details
Equipment ID
11564
11564
Inspection Date
5/6/2022
5/6/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
90a9baf0-9c2a-483c-90d6-e3b5f41af6a5
90a9baf0-9c2a-483c-90d6-e3b5f41af6a5
Location
8th Street Bank
721 Locust St, St. Louis, MO
Phone: (314) 418-1933
721 Locust St, St. Louis, MO
Phone: (314) 418-1933
Owner
Attn: Catherine Blurton
US Bank c/o Cushman & Wakefield
1 US Bank Plz, Ste 200, St. Louis, MO 63101
Phone: (314) 418-8034
Alt Phone: (314) 328-7060 Ext: 102
Email: Catherine.Blurton@cushwake.com
US Bank c/o Cushman & Wakefield
1 US Bank Plz, Ste 200, St. Louis, MO 63101
Phone: (314) 418-8034
Alt Phone: (314) 328-7060 Ext: 102
Email: Catherine.Blurton@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 9/25/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/25/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop shall be kept free of excess dirt & debris. | 9/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Repair machine room smoke detector, damaged and hanging by its wiring. | 9/25/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop shall be kept free of excess dirt & debris. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Repair machine room smoke detector, damaged and hanging by its wiring. Not verified at time of phone reinspection, owner to self-certify. | 10/7/2025 |