Inspection
Inspection Details
Equipment ID
8785
8785
Inspection Date
9/14/2017
9/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
340
340
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
18
18
External ID
8785
8785
Location
Corporate Plaza Bldg
14528 S Outer 40, Chesterfield, MO
Phone: (314) 336-2362
14528 S Outer 40, Chesterfield, MO
Phone: (314) 336-2362
Owner
Realty Assoc Iowa Corp
120 S Central Ave, Ste 500, St. Louis, MO 63105
120 S Central Ave, Ste 500, St. Louis, MO 63105
Billing
Attn: Realty Assoc Iowa Corp
120 South Central, , MO 63105
120 South Central, , MO 63105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Remove oil from pit floor | 12/2/2019 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair Car door restrictors | 9/10/2019 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Post current State certificate in machine room | 12/2/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Repair/replace control valve | 12/2/2019 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room. | 11/1/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance control program shall include written procedures for inspections and test on site. | 11/1/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Current means to collect oil has no lid. | 8/16/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Observed oil in sump hole, remove. Determine if sump still works, replace if needed. | 8/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | None | 8/16/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Current means to collect oil has no lid, provide. | 8/16/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Observed oil in the sump hole, remove. | 8/16/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Determine if the sump pump still works, if not replace. | 8/16/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 8/16/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current State operating permit shall be obtained and displayed in the equipment room. | 5/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). | 5/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. | 5/16/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service operation shall be tested monthly and documented on fire service testing log. No log present. | 5/16/2025 | ||
| MO Minimum : Elevators | (I) - Pits | (I)8 | Determine if the sump pump still works. If not, replace. | 5/16/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Pump motor and/or pump making extremely loud noise while running. Investigate and repair/replace as needed. | 5/16/2025 |