Inspection
Inspection Details
Equipment ID
12187
12187
Inspection Date
5/24/2022
5/24/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Mark Woronowicz
Mark Woronowicz
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
26
26
External ID
5a4f1c5f-b124-49db-aefc-cf110c45e1f1
5a4f1c5f-b124-49db-aefc-cf110c45e1f1
Location
Hillside Manor
1265 McLaran Ave, St. Louis, MO
Phone: (314) 388-5926
1265 McLaran Ave, St. Louis, MO
Phone: (314) 388-5926
Owner
Attn: Administrator
Hillside Rehab and Healthcare Center
1265 McLaran Ave, St. Louis, MO 63147
Phone: (314) 465-5718
Email: jbennett@hillsiderehabhc.com
Hillside Rehab and Healthcare Center
1265 McLaran Ave, St. Louis, MO 63147
Phone: (314) 465-5718
Email: jbennett@hillsiderehabhc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | Yes | Yes | Full load test tags were not on equipment. Attach test tags or Cat 5 will need to be conducted. Did not red tag. | 5/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Jumpers in the fire service panel must be removed. | 4/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Electrical wiring for the machine room light must be in an enclosed conduit, raceway or comply with NFPA 70. | 4/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Electrical prints shall be provided in the machine room. | 4/27/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related material needs to be removed from machine room. | 8/22/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Traveling cable in machine room not in protective raceway. | 8/22/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Missing covers for raceway in machine room. | 8/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | The hoistway is dirty. Clean the hoistway. | 8/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top is dirty. Clean the car top. | 8/22/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall establish 2-way communication. |