Inspection
Inspection Details
Equipment ID
13725
13725
Inspection Date
6/2/2022
6/2/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
97cde179-8edc-4185-b260-dec13cc043bd
97cde179-8edc-4185-b260-dec13cc043bd
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
Owner
Attn: Kenneth Gerry
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@att.com
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@att.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not work. | 6/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell do not work. | 6/2/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Brake failed to hold 125% static load at floor level (drifted to buffer). RED TAG ISSUED. | 5/15/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Items to still be tested: All weight tests (100% & 125%), slide, pullout rope length, fire service, door pressure, and finals (CW Buffer passed). If not completed within 90 days, all of the completed inspection results will be voided and must be repeated. | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. Restrictor plunger removed and laying on cartop. | 5/15/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 5/15/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs and no testing records 2022-2025. | 5/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service shall be tested and documented monthly. No log for 2022-2025. | 5/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Tighten/repair car interior handrail. | 5/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 5/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | 5/15/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Items to still be tested: All weight tests (100% & 125%), slide, pullout rope length, fire service, door pressure, and finals (CW Buffer passed). If not completed within 90 days, all of the completed inspection results will be voided and must be repeated. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Car door restrictor shall work at all floors. Restrictor plunger removed and laying on cartop. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs and no testing records 2022-2025. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service shall be tested and documented monthly. No log for 2022-2025. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Tighten/repair car interior handrail. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. |