Inspection
Inspection Details
Equipment ID
5423
5423
Inspection Date
5/24/2022
5/24/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
John Carpentier, Sr.
John Carpentier, Sr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
f3673bc7-28aa-4440-800f-517b9249731f
f3673bc7-28aa-4440-800f-517b9249731f
Location
York House on Lindell
4931 Lindell Blvd, St. Louis, MO
Phone: (345) 109-0329
Alt Phone: (314) 583-8628
4931 Lindell Blvd, St. Louis, MO
Phone: (345) 109-0329
Alt Phone: (314) 583-8628
Owner
Attn: Koplar Properties
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Billing
Attn: Koplar Properties
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: kelly@koplar.com
Koplar Properties
50 MARYLAND PLZ STE 300, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: kelly@koplar.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Shorten the hoist ropes. | 6/11/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.6 - Final and emergency terminal stopping devices | 8.11.2.1.3(h) | Yes | Yes | Shorten the hoist ropes to allow proper operation on upper final limit. | 6/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Test the rope gripper for proper operation with 125% capacity. | 6/15/2020 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | This elevator previously had the ability to operate on standby/emergency power. The generator has now been disconnected but may be re-connected at some point. So long as the elevator does not operate on standby/emergency power, the emergency power fixture at the egress floor for this car shall be removed or covered. If/when the elevators are re-connected to the emergency generator, the emergency power indicator jewel shall be re-installed and standby/emergency power operation of the elevators shall be tested. | 4/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing gibbs and fire tabs at basement and first floor. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit still. Investigate/repair water leak. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump cover to be reinstalled, and shall be substantially flush to pit floor. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 5/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove rust from pit equipment. repaire/replace as needed. Apply rust orevention treatment to all pit sill. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump cover shall be substantially flush to pit floor. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on site documentation shall be provided in the machine room. |