Inspection
Inspection Details
Equipment ID
13767
13767
Inspection Date
5/24/2022
5/24/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
Swing Doors
Swing Doors
External ID
12bb1f2b-1226-41ba-b585-097494c3288e
12bb1f2b-1226-41ba-b585-097494c3288e
Location
Oxford Condos
320 Union Blvd, St. Louis, MO
Phone: (636) 675-3795
320 Union Blvd, St. Louis, MO
Phone: (636) 675-3795
Owner
Attn: Ted Knobloch
Oxford Condominium Association
5290 Waterman Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: TKnobs06@Yahoo.com
Oxford Condominium Association
5290 Waterman Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: TKnobs06@Yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Provide hoistway access means at top and bottom floors. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Install floor in overhead machine room. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Basement and overhead machine rooms shall have self closing and self locking doors. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell shall work. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Guard or eliminate liquid carrying pipes in machine room. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Hoistway shall be enclosed. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Obtain and display a current state operating certificate. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car lights shall be guarded. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Enclose hall push button wiring at floors B, 2, and 3. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | In car stop switch shall be labeled. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Provide permanent stairs or ladder to overhead machine room. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Hoist cables shall be re-socketed every 24 months. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Lighting is required in overhead machine room to produce 10 ftc in all areas of the room. | 11/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Provide machine room fire extinguisher. | 11/27/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate. | 6/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The overhead machine room door shall be self-locking and self-closing. | 6/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | A minimum of 10 fc of lighting is required in the overhead machine room. | 6/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide a permanent ladder or stairway to overhead machine room. | 6/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/2/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Each passenger car shall be fully enclosed. The open sections on the side and top of the car shall be covered with approved material. | 6/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. | 9/16/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car platform toe guard shall be re-attached. | 9/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm bell is not working. | 11/3/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/2/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Each passenger car shall be fully enclosed. The open sections on the side and top of the car shall be covered with approved material. Cited multiple years. | 6/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The overhead machine room door shall be self-locking and self-closing. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | A minimum of 10 fc of lighting is required in the overhead machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide a permanent ladder or stairway to overhead machine room. |