Inspection
Inspection Details
Equipment ID
10251
10251
Inspection Date
4/26/2022
4/26/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
c136effe-4674-49cb-bcf5-ffbfd3bd8574
c136effe-4674-49cb-bcf5-ffbfd3bd8574
Location
Metropolitan Square
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
Owner
Attn: Metropolitan Square LLC
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (000) 000-0000
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (000) 000-0000
Billing
Attn: Jones Lang LaSalle
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: etcollett@metrostlouis.org
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: etcollett@metrostlouis.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are undersized. 60 day reinspection required or red tagged. | 4/26/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Car sill groves worn allowing excess movement of car doors. Reinspection required. | 3/13/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not work. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to test fire service. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Car sill grooves are worn, allowing excessive movement or car door. Replace sill. | 3/13/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor rope is damaged, has lays broken. Replace same. Red tag | 12/8/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 tests to be performed to complete inspection include: full speed counterweight buffer, full load full speed car buffer, full load full speed car safeties, car door closing force, emergency light, emergency phone, phase 1 and 2 fire service, emergency generator power operatiion | 12/8/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | New counterweight buffers were installed without a rated speed test witnessed by a licensed inspector. The counterweight's buffers are required to have an electric switch installed on each buffer. Install switches and test. Also need rated speed test of new counterweight buffers. Elevator Red-tagged and removed from service. Re-inspection required | 1/31/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | New governor rope was installed without the pull through force tested and witnessed by a licensed inspector. Perform pull through force test and visual inspection. Re-inspection required. Elevator was previously Red-tagged on 5/8/23 | 1/31/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 full load test has not been completed. Test car buffer at rated speed with rated load, test car safeties at rated speed with rated load, door closing force, emergency light, emergency alarm, emergency phone and test for operation under emergency power. Re-inspection required | 1/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Car sill grooves are worn, allowing excessive movement of car doors. Need to replace sill | 3/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 tests to be performed to complete inspection include: full speed counterweight buffer, full load full speed car buffer, full load full speed car safeties, car door closing force, emergency light, emergency alarm, emergency phone, Phase I & II fire service, emergency generator power operation. Re-inspection required | 1/31/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Perform the required standby power testing | 3/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Car struck overhead durring counterweight buffer test. Determine cause and retest. | 3/13/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | Yes | No | Sills excessively worn allowing door panel gap to be outside of code parameters. Replace sills | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Multiple electrical boxes are missing covers on the car top | 3/23/2026 |