Inspection
Inspection Details
Equipment ID
24071
24071
Inspection Date
7/24/2018
7/24/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
05c4be6e-7cdf-4ca5-b4dc-634d195b249d
05c4be6e-7cdf-4ca5-b4dc-634d195b249d
Location
Missouri Rush Soccer Club
901 CALEDONIA DR, O FALLON, MO
901 CALEDONIA DR, O FALLON, MO
Owner
40-DD Sports
137 SNAKE RIVER DR, O FALLON, MO 63368-7737
137 SNAKE RIVER DR, O FALLON, MO 63368-7737
Billing
Attn: 40-DD Sports
137 SNAKE RIVER DR, O FALLON, MO 63368-7737
137 SNAKE RIVER DR, O FALLON, MO 63368-7737
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | Yes | No | A permanent floor in the cab shall be installed. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Sump drain needs anchoring. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Need sign on elevator elevator machine room door indicating elevator equipment. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Install a ceiling in the hoistway and seal all penetrations and voids in the hoistway. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Complete sump pump system and oil minder. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Missing sprinkler head in the pit. | 7/24/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Car emergency telephone shall work. | 7/27/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Install hoistway door fire tabs. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.25.2 | Yes | No | Bottom directional limit inoperative, repair. | 5/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Main line disconnecting switch missing code mandated safety decals. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | No | No | Anchor run of supply piping. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.11.10 | No | No | Anchor hoistway sheet metal between floors. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.7 - Car leveling and anticreep devices | 8.11.2.1.3(j) | No | Yes | Repair anti-creep leveling. | 5/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.31 - Relief Valves | 8.11.3.1.2(n) | No | No | Seal control valve relief setting in machine room. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | Hang landing sill guards flush. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be obtained and displayed. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone does not work. Initiate the necessary corrective action. | 11/28/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Install a code data plate. It shall read: A17.1-2004. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit of dirt and debris. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all non-elevator related materials from the machine room. Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.4 - Normal terminal stopping devices | 2.25 | Yes | No | The bottom directional limit shall activate before the car hits the buffer. Take corrective action as needed. | 11/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-locking, self-closing, and operable from the interior space without the use of a key. | 12/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No state operating certificate in the machine room. | 4/23/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is disconnected and shall be operational. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is not working. |