Inspection
Inspection Details
Equipment ID
20490
20490
Inspection Date
5/27/2022
5/27/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
acb61c59-6d2d-4fd9-851a-a26136091cd4
acb61c59-6d2d-4fd9-851a-a26136091cd4
Location
Desoto Senior Apartments
221 S 3rd St, De Soto, MO
Phone: (636) 586-1617
221 S 3rd St, De Soto, MO
Phone: (636) 586-1617
Owner
Attn: DeSoto Senior Apartments
DeSoto Senior Apartments
221 S 3rd St, DeSoto, MO 63020
Phone: (636) 586-1617
Fax: (636) 586-7555
Email: desotocentral63020@gmail.com
DeSoto Senior Apartments
221 S 3rd St, DeSoto, MO 63020
Phone: (636) 586-1617
Fax: (636) 586-7555
Email: desotocentral63020@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | No | No | A maintenance log shall be kept on-site. | 8/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | No | No | A fire service testing log shall be kept on-site. | 8/2/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | 2.24.8.4 - The means for manual release of the brakes shall be operational. | 8/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Fire gibs shall be installed. | 2/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency battery lowering shall be operational. | 2/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Phase 1 operating instructions shall be by the fire service key switch. | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | No | No | The emergency brake release handle shall work. | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | Emergency battery lowering shall be operational. | 9/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine space illumination shall be 19 foot candles | 6/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Pan shall be placed under the sprinkler lines above the elevator controller. | 5/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Control space shall be 1 hour ?re rated right wall shall extend to the ceiling providing full 1hr ?re rating of the control space | 6/11/2024 |