Inspection
Inspection Details
Equipment ID
23883
23883
Inspection Date
7/5/2018
7/5/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
af846bdb-ec92-4f20-87c1-d2acfaecf931
af846bdb-ec92-4f20-87c1-d2acfaecf931
Location
4101 Laclede Condo
4101 LACLEDE AVE, SAINT LOUIS, MO
4101 LACLEDE AVE, SAINT LOUIS, MO
Owner
Grove Properties
4304 MANCHESTER AVE, SAINT LOUIS, MO 63110-2138
4304 MANCHESTER AVE, SAINT LOUIS, MO 63110-2138
Billing
Attn: Grove Properties
4304 MANCHESTER AVE, SAINT LOUIS, MO 63110-2138
4304 MANCHESTER AVE, SAINT LOUIS, MO 63110-2138
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | No | The installation of the smoke detectors, heat detectors, and shunt trip shall be completed and tested. | 6/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all voids and penetrations in the hoistway and properly secure the ceiling of the hoistway. | 6/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | Receptacle for sump pump shall be located at a minimum 48" or greater above the pit floor. | 6/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Complete installation of battery back up system and test back up system. | 6/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | The finished floor at each landing shall be level with the hoistway entrance sill. | 6/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 7/5/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate. | 11/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | 11/25/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/25/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Provide proper hoistway door safety retainers to confrom to A17.2 - 4.2.1(c) | 3/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication means between the car and a location staffed by authorized personel shall be provided. Per State of MO, if not fixed within 15 days unit will be taken out of service. |