Inspection
Inspection Details
Equipment ID
13625
13625
Inspection Date
5/24/2022
5/24/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
365
365
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
5a0de01d-172e-45c0-b355-fb459c5a4231
5a0de01d-172e-45c0-b355-fb459c5a4231
Location
Zion Lutheran Church- Harvester
3866 S OLD HIGHWAY 94, SAINT CHARLES, MO
Phone: (314) 588-2542
3866 S OLD HIGHWAY 94, SAINT CHARLES, MO
Phone: (314) 588-2542
Owner
Attn: Jeff Calvin
Zion Lutheran Church- Harvester
3866 S OLD HIGHWAY 94, SAINT CHARLES, MO 63304
Phone: (636) 441-7425
Email: jcalvin@zionharvester.org
Zion Lutheran Church- Harvester
3866 S OLD HIGHWAY 94, SAINT CHARLES, MO 63304
Phone: (636) 441-7425
Email: jcalvin@zionharvester.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall be programmed to a 24 hour source. | 5/8/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell shall work. | 8/27/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 6/7/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/29/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 5/29/2025 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 5/29/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 4/26/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Phase 2 fire service hold feature does not work, car is still able to run. 14 days to repair or will be red tagged per MO AHJ. Elevator not currently red tagged. | 4/4/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/29/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/29/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related materials shall not be kept in the machine room. | 5/29/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm shall work. | 3/13/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light shall work. | 3/13/2025 |