Inspection
Inspection Details
Equipment ID
15715
15715
Inspection Date
8/25/2017
8/25/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
460
460
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
25
25
External ID
15715
15715
Location
Convention Center
600 North 6th St, St. Louis, MO
Phone: (314) 982-1400
600 North 6th St, St. Louis, MO
Phone: (314) 982-1400
Owner
Metro Accounts Payable
707 N, 1st St., St. Louis, MO 63188
707 N, 1st St., St. Louis, MO 63188
Billing
Attn: Metro Accounts Payable
P.O. Box 1349, , MO 63188
P.O. Box 1349, , MO 63188
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light not working. | 12/18/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell not working. | 12/18/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Cab ventilation not working. | 12/1/2020 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated certificate in machine room. | 12/1/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Need a maintenance control program on site | 1/13/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Oil line fitting going into tank leaking oil onto floor needs repair | 1/13/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine room can not be used for storage of non elevator equipment | 12/7/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | Replace leaking victaulic fitting on hydraulic line in the machine room. Fitting is on the bottom side of the shut off valve | 12/7/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Phone in the elevator cab does not work. Repair or replace | 2/1/2022 | |
A17.1-2016 : Elevators | 1.14 - Ventilation | 2.14.2.3 | x | Elevator cab ventilation fan does not work on auxiliary power (battery power) needs repaired. Re-inspection required | 10/4/2024 | |
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Elevator cab door restrictor does not work, needs repaired. Re-inspection required | 10/4/2024 | |
A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | x | Safety retainers are missing on top & bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |