Inspection
Inspection Details
Equipment ID
14348
14348
Inspection Date
5/27/2022
5/27/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
ba5bb362-3eea-4fdf-90fd-3203c7f3ccfd
ba5bb362-3eea-4fdf-90fd-3203c7f3ccfd
Location
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO
Phone: (314) 574-4252
Email: TMTompkins@magellanhealth.com
14100 Magellan Plz, Maryland Heights, MO
Phone: (314) 574-4252
Email: TMTompkins@magellanhealth.com
Owner
Attn: Michael Loeffler
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: MCLoeffler@magellanhealth.com
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: MCLoeffler@magellanhealth.com
Billing
Attn: John Shanahan
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: JShanahan@magellanhealth.com
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: JShanahan@magellanhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.1 - Top-of-car stop switch | 1001.2(c)(1) | No | No | Repair or replace the front car top stop switch. | 2/6/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 2/15/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 2/15/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 5/27/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall be operational. | 5/27/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/18/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 9/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. | 9/18/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. | 9/18/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/9/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 3/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. | 3/9/2026 |