Inspection
Inspection Details
Equipment ID
6364
6364
Inspection Date
6/15/2022
6/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
9b1d46bd-f0d7-461a-9bf5-db6f5a11569f
9b1d46bd-f0d7-461a-9bf5-db6f5a11569f
Location
Corby Building
422 Felix St, St. Joseph, MO
Phone: (816) 233-4600
422 Felix St, St. Joseph, MO
Phone: (816) 233-4600
Owner
Attn: Corby Senior Living
Corby Senior Living
PO Box 374, Pico Rivera, CA 90660
Phone: (000) 000-0000
Corby Senior Living
PO Box 374, Pico Rivera, CA 90660
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light and bell do not operate. | 12/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Need to post fire service instructions inside the elevator | 12/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Need to remove debris from machine room floor. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need to post emergency evacuation of passengers form inside machine room. | 8/25/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace rouged and undersized governor rope. | 7/16/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties do not stop the elevator. Slide is 56 inches and exceeds allowed limits | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Install seal on machine brake spring tension adjustment nut. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn traction sheave liners | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken hoist rope shackle springs on the car and counterweight connections | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Equalize hoist rope tension | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Lobby dial position indicator is not operating and needs repair. | 12/7/2023 |