Inspection
Inspection Details
Equipment ID
25740
25740
Inspection Date
6/17/2022
6/17/2022
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Chad Boxdorfer
Chad Boxdorfer
Relief Valve Pressure
Slide
7
7
Governor Rope Pull
50/175
50/175
Door Closing Force
28
28
External ID
47bcd74b-dc1c-48ae-81f6-55ec1aa779f3
47bcd74b-dc1c-48ae-81f6-55ec1aa779f3
Location
The Hill Apartments
2100 Boardman St, St. Louis, MO
Phone: (000) 000-0000
Email: dhotop@holland.com
2100 Boardman St, St. Louis, MO
Phone: (000) 000-0000
Email: dhotop@holland.com
Owner
Attn: Draper and Kramer, Inc.
Draper and Kramer, Inc.
55 E Monroe St, Ste 3900, Chicago, IL 60603
Phone: (000) 000-0000
Email: dhotop@holland.com
Draper and Kramer, Inc.
55 E Monroe St, Ste 3900, Chicago, IL 60603
Phone: (000) 000-0000
Email: dhotop@holland.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase Machine space illumination to 19 footcandles minimum | 6/30/2022 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase Control space to 19 footcandles minimum | 6/30/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Close Control space penetrations | 6/30/2022 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.3 | Yes | No | Control space door shall be self-closing, self-locking | 6/30/2022 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Close all hoistway penetrations | 6/30/2022 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | Yes | No | If determined by the local building codes hoistway vent is not required. remove wood blocking and replace with 2hr rated closure | 6/30/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Increase pit illumination to 10 footcandles minimum | 6/30/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | Yes | No | Cover pit sump even with pit floor | 6/30/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Install smoke detector in the Control space | 6/30/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | All Phase I Recall Devices Shall Be Tested | 6/30/2022 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/12/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The video/text emergency communication means shall conform to A17.1 - 2019, Section 2.27. The text operation is not working. See MO Memorandum 013. A variance shall also be applied for. | 11/12/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The video/text emergency communication means shall conform to A17.1 - 2019, Section 2.27. The text operation is not working. See MO Memorandum 013. A variance shall also be applied for. | 4/14/2026 |