Inspection
Inspection Details
Equipment ID
9655
9655
Inspection Date
6/21/2022
6/21/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
28
28
External ID
85cc1c81-8fe3-4a73-a2f6-caeeb73b7b99
85cc1c81-8fe3-4a73-a2f6-caeeb73b7b99
Location
SSM-De Paul Health Center
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6102
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6102
Owner
Attn: Jeff Fleming
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6456
Email: jeffrey.fleming@ssmhealth.com
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6456
Email: jeffrey.fleming@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | There are a number of Braille floor indicating/push button tags that are missing on multiple floors and shall be reinstalled for proper floor identification. | 7/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Replace suspension ropes due to reduced diameter. Will require a permit from the state of Missouri. Reinspect in 90 days | 8/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | The hoistway door jamb at the 3rd floor is damaged and is peeling away from the wall. The door jamb shall be repaired to a smooth finish. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. | 6/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 6/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. |